23
REFERENCE
Setting the behavior of the drive during referencing
0 = reference point in closed pos monitors infra
1 = reference point in closed pos do not monitor infra
2 = reference point in opened pos monitors infra
3 = reference point in opened pos do not monitor infra
Default = 0
Pushing door in closed possition
Setting the behavior of the drive in the closed position
0 = no reaction
1 = in the case of a mechanical pull from the closed position, it goes into the
counter-pull and tries to close again
2 = in the end position it constantly pushes gently to the closed possition
(frequency 3Hz) this function is activated to heat the engine to heat the oil
in the gearbox, use in installations with a temperature below freezing
Pushing door in closed possition
Nastavení chování pohonu v otevřené pozici
0 = no reaction
1 = in the case of a mechanical pull from the opened position, it goes into the
counter-pull and tries to open again
2 = in the end position it constantly pushes gently to the opened possition
(frequency 3Hz) this function is activated to heat the engine to heat the oil
in the gearbox, use in installations with a temperature below freezing
Duration of overload – start-up
Range of values: 1–50 (0,1–5 sec.) steps in 0,1sec
Setting of the time for which the evaluation of the overload during start-up is limited.
Default = 30 (3 sec)
Duration of overload – normal run
Range of values: 1–10 (0,1–1 sec.) steps in 0,1sec
Setting the time for which the evaluation of running overload is limited. By increasing the
value, it is possible to limit the evaluation of overload so that there is no inappropriate
evaluation of overload with a short-term increase in resistance when moving the door
Default = 3 (0,3 sec)
Overload
Range of values: 1–10 (10-100%) steps in 10%
Setting the value of the permitted exceeding of the maximum torque measured during
time and torque calibration. Increasing the value increases the torque (force) of the drive
before evaluating the overload.
Default = 3 (30%)
Summary of Contents for FSTronic IRC-FI
Page 36: ...www somati system cz 36 12 2 FSTronic IRC FI CONTROL BOARD DPS ...
Page 38: ...www somati system cz 38 12 4 FSTronic IRC FI CONNECTION OF FIRE DETECTORS ...
Page 39: ...www somati system cz 39 12 5 FSTronic IRC FI Connection aof additional battery module ...
Page 42: ...www somati system cz 42 GridScan PRO SY 2000 FSS GridScan PRO SY 2000 LO ...
Page 43: ...www somati system cz 43 GridScan MINI FSS GridScan MINI PNP NPN ...