User Manual
EM100 Mini Inverter
58
C00.13
Output Terminal
Status
* * * * * * R1 Y1(Monitoring
output terminal logic status)
×
C00.14
VS Input
Monitoring
0.00
~
10.00 V
×
C00.15
IS Input
Monitoring
0.00
~
20.00
mA
×
C00.16
Inverter Heatsink
Temperature
0
~
200
0
C
×
C00.17 VP Input Monitoring
0
~
5.00 V
×
E00 Group
:
Fault Monitoring Parameters
E00.00/
E00.01
/E00.02
The 1
st
/2
nd
/3
rd
Most Recent
Fault Records
00: No fault
SC: Short circuit
SOC: Stable overcurrent
SOU: Stable overvoltage
SLU: Stable undervoltage
ILP: Input phase loss
OL: Inverter overload
OL1:Motor overload
OH: Overheating
OLP: Output Phase Loss
EHt: External Fault
EEd: Inverter EEPROM failure
StP: Autotuning cancelled
SrE: Stator resistance error
SIE: Idling current error
InP: Internal failure
PIdE: PID feedback loss
COE: Communication overtime
error
SOFt: Inverter soft-start relay is off.
tbr: Temperature sensor break
00 ×
E00.03
Output
Frequency at
Last Fault
0.00
~
320.00 Hz
0.00
×
E00.04
Output Current
at Last Fault
0.0
~
300.0 A
0.0
×
E00.05
DC Bus
Voltage at Last
Fault
0
~
1200 V
0
×