User Manual
EM100 Mini Inverter
55
F08.14
Program
Operation Time
T6
0
~
60000 S
30
●
F08.15
Program
Operation Time
T7
0
~
60000 S
30
●
F08.16
Speed Cycling
Times
1
~
60000
1
●
F09 Group: PID Parameters
F09.00
PID Reference
Setting Mode
0: Numeric PID setting
1: Terminal VS
2: Terminal IS
3: Terminal VP
0
〇
F09.01
PID Numeric Setting
0.0
~
100.0 %
50.0
●
F09.02
PID Feedback Options
0: Terminal VS
1: Terminal IS
0
〇
F09.03
PID Setting/Feedback Scale
0
~
60000
1000
●
F09.04
PID Regulator Positive/
Negative Setting
0: Positive setting
1: Negative setting
0
〇
F09.05
PID Output Gain
0.00
~
100.00 %
100.00
●
F09.06
Proportion
Gain GP
0.00
~
100.00
0.40
●
F09.07
Integral Time GTi
0.00
~
300.00
0.00: No integration
S 10.00
●
F09.08
Differential
Time GTd
0.00
~
300.00
0.00:No differentiation
mS
0.00
●
F09.09
Integration Function
Scale
0.00
~
100.00 %
100.00
●
F09.10
PID Positive Output Limit
0.00
~
100.00 %
100.00
●
F09.11
PID Negative Output Limit
0.00
~
100.00 %
100.00
●
F09.12
PID Feedback Loss
Detection Value
0.0
~
100.0 %
0.0
●
F09.13
PID Feedback Loss
Detection Time
0.0
~
3000.0 S
1.0
●
F10 Group: Communication Parameters
F10.00 Inverter
Address
1
~
247
,
0:Broadcasting address
1
〇