User Manual
EM100 Mini Inverter
68
No.
Function
Range
Unit
Default Type
F00.21
Saving Setting
Frequency Options
0: Do not save the frequency
before power loss
1: Save the frequency before
power loss
0
〇
F00.22
Default Reset
0: Disabled
1: Reset default
0
〇
Saving Setting Frequency Options
F00.21=0
Do not save the frequency before power loss
F00.21=1 Save the frequency before power loss
When power loss occurs, inverter will save primary numeric frequency,
auxiliary numeric frequency, and program operation sections/time/cycling times.
Default Reset
F00.22=1 Reset default:
Reset defaults of all parameters in F00, F02
~
F10 Group, and
F00.22=0 automatically after resetting completed.
Remarks:
Motor parameters (F01 Group) and user parameters( F11.03
~
F11.12 Group )
will not be reset to defaults if conducting default reset.
F01 Group: Motor Parameters
No.
Function
Range
Unit
Default
Type
F01.00
Motor Rated Power
0.40
~
655.35
kW XXXX
〇
F01.01
Motor Rated Voltage
60
~
480
V XXX
〇
F01.02
Motor Rated Current
0.1
~
100.0
A XXXXX
〇
F01.03
Motor Rated Frequency
20.00
~
320.00
Hz XXXXX
〇
F01.04
Motor Rate Speed
1
~
20000
rpm XXXXX
〇
F01.05
Motor Wiring Mode
0: Y Wiring
1:
Δ
Wiring
X
〇
F01.06
Motor Rated Power Factor 0.70
~
0.95
XXX
〇
F01.07
Motor Efficiency
70.00
~
97.00
% XXXX
〇
Remarks:
When inverter connects to motor at the first time, set all parameters as per
motor nameplate before operation starts.
No.
Function
Range
Unit
Default
Type
F01.08
Idling Excitation Current
0.1
~
100.0
A XXXXX
〇
F01.09
Stator Resistance R1
0.01
~
300.00
Ω
XXXXX
〇
F01.10
Rotor Resistance R2
0.01
~
300.00
Ω
XXXXX
〇
F01.11
Stator& Rotor Mutual
Inductance Lm
0.1
~
3000.0
mH XXXX
〇
F01.12
Leakage Inductance
Coefficient
0.001
~
1.000
XXXX
〇