User Manual
EM100 Mini Inverter
88
2: Overvoltage stall mode 2
F07.06
Overvoltage Stall
Voltage
380V: 640
~
800
220V: 370
~
400
V
750
〇
390
F07.07
Overvoltage Stall
Mode 2 Proportion
Gain
0.01
~
10.00
0.30
●
F07.08
Overvoltage Stall
Mode 2 Integral
Time
0.00
~
300.00
0.00: Integration Disabled
S
10
.
00
●
F07.05=0 Overvoltage Stall Disabled.
F07.05=1 Overvoltage Stall Mode 1
Figure 6-21 Overvoltage Stall Mode 1
In deceleration process, after DC bus voltage exceeds overvoltage stall voltage (F07.06),
inverter stops deceleration process, and remains at present running frequency. After DC bus
voltage decreases, inverter will decelerate as per previous deceleration time, see Figure
6-21.
F07.05=2 Overvoltage Stall Mode 2
Overvoltage stall mode 2 is applied to the applications which are sensitive to acceleration/
deceleration time.
In this mode, the motor frequency is automatically adjusted by DC bus voltage as per the PI
parameters set in F07.07 and F07.08.
For load with larger inertia if overvoltage stall occurs during deceleration, the propotional
gain may be increased.
For load with smaller inertia, the propotional gain may be kept smaller.
Integral time can be adjusted for fine tunning in both cases.
No.
Function
Range
Unit
Default
Type
F07.10
Motor Overload
Protection Options
0: Prohibited
1: Permitted
1
〇
F07.11
Motor Overload
Protection Time
30
~
300
S 60
〇