No.
Function
Range
Unit
Default Type
F06.05
UP/DOWN
Frequency Rate
0.00
~
100.00 Unit: Hz/ 200mS
0.00(Autorate integration)
1.00
●
In primary speed setting mode, edit primary speed setting (F00.07) via multi-function
terminal UP/DOWN. Unit: Hz/200mS
F06.05=0.00:
In autorate integration mode, edit F00.07 value slowly at beginning and then
faster later based on the lasting time when terminal UP/DOWN is on.
F06.05
≠
0.00:
Edit numeric setting value as per UP/DOWN rate set by F06.05 based on the
lasting time when terminal UP/DOWN is on, calculate by Hz/200mS, only round-up, no
round-off.
No.
Function
Range
Unit
Default
Type
F06.06
Frequency Reach Signal
FAR
0.00
~
20.00
Hz 5.00
●
If multi-function output or relay output is set as 1(FAR), if absolute value of the difference
between output frequency and input frequency of inverter is less than the setting value of
F06.06, the corresponding output terminal is on. See Figure 6-16.
No.
Function
Range
Unit
Default
Type
F06.07
FDT Increasing
Threshold
0.00
~
Fmax
Hz 30.00
〇
F06.08
FDT Decreasing
Threshold
0.00
~
Fmax
Hz 30.00
〇
If multi-function output or relay output is set as 2(FDT), when the output frequency of
inverter rises to the FDT increasing threshold (F06.07), the corresponding output terminal
is on, and it will be off when the output frequency drops to the FDT decreasing threshold
(F06.08). See Figure 6-17.
Figure 6-16 FAR
Figure 6-17 FDT
No.
Function
Range
Unit
Default
Type
F06.09
Output Voltage
5.00
~
100.00
% 100.00
●
Output voltage: If the inverter is not required to output the present voltage value, adjust the
percentage of output voltage to input voltage.