User Manual
EM100 Mini Inverter
45
F00.08
Auxiliary
Numeric Frequency
Setting
0.00
~
Fmax Hz
0.00
●
F00.09 Acceleration
Time
1
0.01
~
600.00 S
15.00
●
F00.10 Deceleration
Time1 0.01
~
600.00 S
15.00
●
F00.11
Maximum
Frequency
Fmax:20.00
~
320.00 Hz
50.00
〇
F00.12
Upper Limit
Frequency
Fup: Fdown
~
Fmax Hz
50.00
〇
F00.13
Lower Limit
Frequency
Fdown: 0.00
~
Fup Hz
0.00
〇
F00.14
Motor Running
Direction
0: Forward
1: Reverse
0
●
F00.15 Reverse
Control
0: Reverse permitted
1: Reverse prohibited
0
〇
F00.16 F/R
Deadband
0.00
~
600.00 S
0.00
〇
F00.17 Carrier
Frequency
2.000
~
12.000 kHz
4.000
●
F00.18
Random Carrier
Mode
0: Fixed carrier
1: Random carrier
2: Fixed carrier, which can be
adjusted by carrier temperature
and carrier current.
3: Random carrier, which can
be adjusted by carrier
temperature and carrier current.
2
●
F00.19
Upper Carrier
Frequency
2.000
~
12.000 kHz
8.000
●
F00.20
Lower Carrier
Frequency
2.000
~
12.000 kHz
2.000
●
F00.21
Saving Setting
Frequency Options
0: Do not save the frequency
before power loss
1: Save the frequency before
power loss
0
〇
F00.22 Default Reset
0:Disabled 1:Reset default
0
〇
F01Group
:
Motor Parameters
F01.00
Motor Rated Power
0.40
~
655.35 kW
XXXX
〇
F01.01
Motor Rated Voltage
60
~
480 V
XXX
〇
F01.02
Motor Rated Current
0.1
~
100.0 A
XXXXX
〇
F01.03
Motor Rated
Frequency
20.00
~
320.00 Hz
XXXXX
〇