3.1.4.3 Table of Heat Dissipating Capacity (HDC), Mass Airflow(MAF) and Noise
of Single EM100
Model No.
Frame
MAF
(
CFM
)
MAF
(
m
3
/h
)
HDC
(
W)
Noise
(
dB/A
)
EM100-0R4-1B
SIZE1
8 13.6 42 38
EM100-0R7-1B
8 13.6 70 38
EM100-1R5-1B
SIZE2
13 22 90 40
EM100-2R2-1B 13
22
120
40
EM100-0R7-3B
13 22 75 40
EM100-1R5-3B 13
22
85
40
EM100-2R2-3B 13
22
105
40
EM100-4R0-3B 13
22
150
40
EM100-5R5-3B
SIZE3
31.2 53 174 45
EM100-7R5-3B 31.2
53
252
45
EM100-011-3B
31.2 53 362 45
EM100-015-3B
SIZE4
106 180 520 55
Remarks:
1.
The values listed in the table refer to that the HDC and the MAF required when single
EM100 is mounted in an enclosed space.
2.
The HDC is calculated based on the rated voltage, rated current and preset carrier
frequency of each model.
3.
If multi-EM100 has to be installed in an enclosed space, please add HDC and MAF.