User Manual
EM100 Mini Inverter
117
5.6 Details of 0x08 Circuit Diagnoses and Setting
Sub-function
Code
Data Requested
Response Data
Indication of
Sub-function
0000H #data16
The same as the data
requested
Circuit Diagnosis
6. Example
6.1 Read the setting value of primary numeric frequency F0-07 of inverter No.1,
return 5000(50Hz).
Transmit
Sequence
0 1 2 3 4 5 6 7 8 9
Data 01H
03H
20H
07H
00H
01H
3EH
0BH
Receive
Sequence
0 1 2 3 4 5 6 7 8
Data 01H 03H 02H 13H 88H B5H
12H
6.2 Write F0-07=30.00Hz, data transmission:3000
(The setting value of primary numeric frequency of inverter No.1)
Transmit
Sequence
0 1 2 3 4 5 6 7 8 9
Data
01H
06H
00H
07H
0BH
B8H
3FH
49H
Receive
Sequence
0 1 2 3 4 5 6 7 8 9
Data
01H 06H
00H
07H
0BH B8H 3FH
49H
6.3 Start inverter operation, and write control command for 4000H address.
Transmit
Sequence
0 1 2 3 4 5 6 7 8 9
Data
01H 06H
40H
00H
00H
01H 5DH
CAH
Receive
Sequence
0 1 2 3 4 5 6 7 8 9
Data
01H
06H
40H
00H
00H
01H
5DH
CAH
6.4 Inverter stops
Transmit
Sequence
0 1 2 3 4 5 6 7 8 9
Data 01H 06H
40H
00H
00H 05H 5CH
09H
Receive
Sequence
0 1 2 3 4 5 6 7 8 9
Data
01H 06H
40H
00H
00H
05H 5CH
09H