14
Acceleration/
Deceleration
Prohibition
If acceleration/deceleration prohibition terminal is on, it is
prohibited performing acceleration/deceleration command.
The inverter will keep output frequency unchanged, and
will not be controlled by input frequency.
15
3-wire
Sequence
Run/Stop
Control(Pulse
Stop)
It is the NC stop key for 3-wire sequence terminal control.
16
DC Brake
Input
Command at
Stop
When inverter is in the process of ramp-to-stop, and
running frequency < DC brake frequency (Set by F04.06)
at stop, if the terminal is on, DC brake starts, until the
terminal is off, DC brake ends.
If the terminal is on, and DC brake setting time is effective,
take the bigger value between time when terminal is on and
DC brake setting time at stop.
17
Switch Run
Command to
Terminal
If the terminal is on, no matter what running command
mode F00.02 status is, it is in terminal control mode which
has the highest priority. Terminal control mode is set by
F00.02.
18
Program
Running
Reset
In program operation mode (PLC), if the input signal of the
terminal is active, then program operation time will be
cleared, cycling time cleared, and program operation starts
from Preset Speed 1.
19
Switch to
Auxiliary
Speed Setting
In speed control mode, if the terminal is on, switch
integrated speed setting mode to auxiliary speed setting
mode, as set F00.05=1. After the terminal is off, it returns
previous setting mode automatically.
20
External
Fault Input
When inverter receives the external fault signals, it trips
fault and coasts to stop.
21
Start
Wobbulation
Operation
Wobbulation running is under terminal control as selecting
F06.18 ones place=1.
Table 6-7 Correlation between Preset Speed Terminal and Preset Speed Setting
Preset
Speed
Terminal 3
Terminal 2
Terminal 1
Selected
Frequency
Corresponding
Setting Code
1 OFF OFF OFF Keypad or
Analog Setting
Defined by
F00.03
2 OFF OFF
ON
Preset
Speed 1
F08.00
3 OFF ON
OFF
Preset
Speed 2
F08.01
4 OFF ON
ON
Preset
Speed 3
F08.02
5 ON OFF
OFF
Preset
Speed 4
F08.03
6 ON OFF
ON
Preset
Speed 5
F08.04
7 ON ON
OFF
Preset
Speed 6
F08.05
8 ON ON
ON
Preset
Speed 7
F08.06