User Manual
EM100 Mini Inverter
93
Operation Stopped and Restart Options
F08.07 Hundreds place=0
If external fault terminal is on in the process of program
operation, after power loss or fault occurred, inverter enters operation status to run as per
the section at stop(including the section at stop, the remaining running time and setting
operation frequency).
F08.07 Hundreds place=1
If external fault terminal is on in the process of program
operation, after power loss or fault occurred, then enter operation status, program operation
starts from Preset Speed 1.
Running Direction Options
F08.08 All Bits=0
Positive input, motor forwards, output is positive torque.
F08.08 All Bits=1
Negative input, motor reverses, output is negative torque.
If setting F00.15 as reverse permitted, reverse is disabled in program operation. If the 0
th
bit
of F08.08 set as 1 or function terminal setting is reverse command. Inverter will run at 0Hz
in Preset Speed 1. Operation of each section will follow the same pattern.
Operation Time
F08.09
~
F08.15
define the operation time of each section in program operation and can be
set in succession, range: 0
~
60000 seconds.
If program operation section is 0 second, program operation will skip this section.
See Figure 6-23 for program operation diagram.
Figure 6-23 Program Operation Diagram
In Figure 6-23, the operation time of Preset Speed 3 is set as 0. Therefore, Preset Speed 3
does not operate.
In program operation, operation frequency, operation time, and positive/negative input can
be set.
Inverter runs as per the operation frequency of preset speed 1-7 set by F08.00-F08.06.
Start process of EM100 program operation: Select F00.04 auxiliary speed setting mode as
program operation, select integrated frequency setting mode as auxiliary speed setting
mode or other options including auxiliary speed setting mode.