No.
Function
Range
Unit
Default
Type
F04.06
DC Brake Start Frequency at
Stop
0.10
~
60.00
Hz 2.00
〇
F04.07
DC Brake Current at Stop
0.00
~
150.00
% 2.00
〇
F04.08
DC Brake Waiting Time
0.00
~
30.00
S 0.00
〇
F04.09
DC Brake Time at Stop
0.00
~
30.00
S 0.00
〇
F04.06
Set the frequency for DC brake to start in the process of ramp-to-stop. Once the
output frequency is lower than this frequency in the process of ramp-to-stop, if DC
brake time
≠
0 at stop, then DC brake enabled.
F04.07
Different setting values can define different DC brake torques at stop.
F04.08
When DC brake command given by the terminal is active at stop or the output
frequency reaches the setting value of F04.06 in the process of ramp-to-stop. DC
brake enabled after the time set by F04.06 is up.
F04.09
Set DC brake time at stop. If F04.09=0.00, the DC brake is disabled at stop. If there
is a DC brake signal of external terminal at stop, then the DC brake time takes the
bigger value between the active time of the terminal and the setting time of F04.09.
See Figure 6-14 for DC brake process at stop.
Figure 6-14 DC Brake Process at Stop
F05 Group: V/F Control Parameters
No.
Function
Range
Unit Default Type
F05.00
V/F Curve Scaling
See Table 6-15
35
●
F05.01
Frequency Base
Fbase:20.00
~
320.00
Hz 50.00
〇