User Manual
EM100 Mini Inverter
81
No.
Function
Range
Unit
Default
Type
F05.13
Oscillation Suppression
0.00
~
100.00
% 0.00
●
If output current is not stable, oscillation suppression is applied to limit current oscillation
and to avoid overcurrent triggered by current oscillation when motor starts. It is also used
to reduce vibration of motor and mechanical devices.
No.
Function
Range
Unit
Default
Type
F05.14
Overmodulation Level
1.00
~
1.10
1.00
●
Overmodultaion level: If grid voltage is too low, in order to help the output voltage reach
the rated voltage, the output voltage could be 1.1 times of present grid voltage after
modulation.
No.
Function
Range
Unit
Default
Type
F05.15
AVR
0: Disabled
1: Enabled
2: AVR is disabled if the
DC bus voltage > the
rated voltage of DC bus,
and it will be enabled if
the DC bus voltage
≤
the
rated voltage of DC bus.
0
〇
Automatic voltage regulation is applied to the occasions when input voltage varies, output
voltage remains unchanged basically, and V/F value keeps constant.
F06 Group: Auxiliary Function Parameters
No.
Function
Range
Unit Default
Type
F06.00
Jog Numeric Frequency
0.00
~
Fmax
Hz 5.00
●
F06.01
Jog Acceleration Time
0.01
~
600.00
S 15.00
●
F06.02
Jog Deceleration Time
0.01
~
600.00
S 15.00
●
In jog running mode, inverter runs as per the setting frequency of F06.00, and runs to the
acceleration/deceleration time of Fmax set by F06.01/F06.02.
Jog acceleration time (F06.01) is the time taken for the output frequency to rise from 0Hz
up to Fmax. Jog deceleration time (F06.02) is the time taken for the output frequency to
drop from Fmax down to 0Hz.
key should be active and terminal JOG should be on in jog running mode. Otherwise,
jog command will be considered as cancelled.
No.
Function
Range
Unit
Default
Type
F06.03
Acceleration 2
0.01
~
600.00
S 15.00
●
F06.04
Deceleration 2
0.01
~
600.00
S 15.00
●
Details refer to the description of F00.09 and F00.10.