User Manual
EM100 Mini Inverter
100
No.
Function
Range
Unit
Default
Type
F11.03
Inverter Rated Power
0.40
~
22.00
kW XXXX X
F11.04
Inverter Rated Voltage
60
~
480
V XXX X
F11.05
Inverter Rated Current
0.1
~
100.0
A XXXXX
X
The parameters are only for reference and cannot be edited. Please verify the parameters
with the nameplate before operation.
No.
Function
Range
Unit
Default
Type
F11.06
Inverter Running Time
User Monitoring
HOUR
XXXXX
X
F11.07
Inverter Running Time
User Monitoring
min
XXXXX
X
F11.08
Running Time Control
0: Disabled
1: Enabled
0
〇
F11.09
Setting Running Time
0
~
65535
HOUR
00000
〇
F11.06
Hours that inverter has run. The parameters are only for reference and cannot be
edited. Running time is the time accumulation of operation status.
F11.07
Minutes within 1 hour that inverter has run. The parameters are only for
reference and cannot be edited.
F11.08=0
Running time control disabled.
F11.08=1
Running time control enabled, if the setting operation time is up, inverter trips
InP (Internal fault), and cannot run.
F11.09
For controlling the operation time of inverter.
The permitted operation time = F11.09 -F11.06.
No.
Function
Range
Unit
Default
Type
F11.10
Distributor Password
0
~
65535
XXXXX
〇
F11.11
Factory Password
0
~
65535
XXXXX
〇
In order to prevent the key parameters from being edited and resulting in faults, the
parameters are only for professionals.
No.
Function
Range
Unit
Default
Type
F11.12
Software Version
-
XXXXX
X
The parameters are only for reference and cannot be edited.