1. Start/Stop of preset speed running is defined by F00.02.
2. When multi-function input terminal setting value is 6, acceleration/deceleration
time of preset speed running is controlled and selected by the terminal.
3. Preset speed running will be affected by whether terminal F/R or RUN is ON (in
terminal start/stop control mode). If terminal F/R is ON, the preset speed is reverse speed.
4. If reverse is required in the process of preset speed, please set inverter start/stop mode as
terminal control mode, and set F00.15=0(Reverse permitted).
No.
Function
Range
Unit Default
Type
F02.06
Multi-function
Input Positive/
Negative Logic
X6
X5
X4 X3
X2
X1
000000
〇
0 0 0 0 0 0
0:Positive Logic
Terminals are on at 0V/off at 24V
1:Negative Logic
Terminals are off at 0V/ on at 24V
X1 is LSB, arrange in logical order,
the 7
th
and the 8
th
bits are not used.
F02.07
Multi-function
Input Filter
Times
0
~
100
10
〇
F02.08
X1 Input Delay
Time
0.00
~
300.00
S 0.00
〇
F02.09
X2 Input Delay
Time
0.00
~
300.00
S 0.00
〇
F02.06 Terminal Input Positive/Negative Logic
0: Positive logic—Terminals are on at 0V/off at 24V.
1: Negative Logic—Terminals are off at 0V/ on at 24V.
For codes displayed in binary system, if the 6
th
~8
th
bits require to be edited, press
to
shift to the 6
th
~8
th
bits. For codes (displayed in binary system) required to be edited in
communication, see the following table for the value and corresponding decimal digit and
hexadecimal digit.
Displayed Binary Value of F02.06
Corresponding
Decimal Digit
Corresponding
Hexadecimal Digit
00000000 0
0
00000001 1
1
00000010 2
2
…… ……
……
11111110 254
FE
11111111 255
FF
F02.07 Numeric Input Filter Times
Since multi-function input terminals take PWL trigger or pulse trigger mode, in order to
avoid interference, numeric filter processing is required for reading terminal status. When
filter times =1, the filter time is 0.50mS.