F00.02 start/stop selected as 2-wire sequence terminal control (F00.02=01or
F00.02=11), when terminal RUN or F/R is on, inverter stops with PLC section
cycling stop command. Even control terminal RUN or F/R is on, the inverter
will not run after stop command cancelled. If inverter needs to run, terminal RUN or
F/R has to be triggered again.
F00.02 Tens place=2 Terminal RUN-NO forward, Xi-NC stop, and F/R-NO reverse
(3-wire sequence control mode 1)
Xi is the enabling terminal in this mode. Xm and Xn define direction. See Table 6-3 for
terminal function setting.
Table 6-3 Setting of 3-wire Sequence Terminal Control Mode 1
Terminal
Setting Value
Description
Xm 1
RUN-NO
forward
Xn 2
F/R-
Reverse
Xi 15
NC
stop
Terminal Xi shall be on first if inverter has to run. Forward or reverse of motor is
controlled by the pulse edge of Xm or Xn.
Terminal Xi shall be off if inverter has to stop.
Xm, Xn, and Xi are the multi-function terminals of X1
~
X6 (F02.00
~
F02.05).
Figure 6-3 3-wire Terminal Control Mode 1
F00.02 Tens place=3 Terminal RUN-NO run, Xi-NC stop, F/R-Forward/ Reverse
(3-wire control mode 2)
Xi is the enabling terminal in this mode. Xm gives run command, and Xn defines direction.
See Table 6-4 for terminal function setting.
Table 6-4 Setting 3-wire Terminal Control Mode 2
Terminal
Setting Value
Description
Xm 1
RUN-NO
run
Xn 2
F/R-Forward/reverse
Xi 15
NC
stop
Terminal Xi shall be on first if inverter has to run. Pulse increasing edge of Xm generates
motor running signal, and the status of Xn defines motor direction signal.
Terminal Xi shall be off if inverter has to stop.
Xm, Xn, and Xi are the multi-function terminals of X1
~
X6(F02.00
~
F02.05). Xm is on
with pulse, and Xi and Xn are on at PWL.
SB1: Key for forward
SB2: Key for reverse
K: Key for stop