User Manual
EM100 Mini Inverter
10
20mA or a voltage input:0
~
10V
Input impedance:
voltage input: 1M
Ω
, current input: 250
Ω
Accuracy: 0.2%
Numeric Output
Terminal
1 programmable OC output
Max. load capacity: 50mA/24V
Output frequency range:0
~
1kHz
1 programmable relay output, EA-NO,
EB-NC, EC-Common port
Contact capacity: 3A/AC250V
Power factor:>0.4 or 1A/DC30V
Analog Output
Terminal
1 programmable analog output terminal,
output: 0
~
10V
Max. load capacity: 2mA
Accuracy: 0.1V
Display
LED
5-bit display, 8 input keys
Protection Protections
Overcurrent, overvoltage, input/output phase
loss, output short-circuit, overheating, and
etc.
Application
Conditions
Installation Site
Indoor, with altitude less than1,000 meters,
free from dust and corrosive gas, and direct
sunlight
Ambient Temperature
-10
℃~
+40
℃
. In the temperature range +40
°C…+50 °C, the rated output current is
decreased by 1% for every additional 1 °C.
20%
~
90%RH (no condensation)
Vibration
﹤
0.5g
Storage Temperature
-20
°
C
~
+65
°
C
Installation Method
Wall mounting
Protection Grade
IP20
Cooling Method
Forced air cooling
Noise 38-62dB/A
(
See 3.1.4.3 for detail.
)
Safety Standard
IEC61800-5-1:2007
EMC Standard
IEC61800-3: 2004