F10.06 Inverter receiving proportion coefficient
This function defines the numeric frequency (received by the slave from the master)* the
proportion coefficient of F10.06, which is the actual frequency setting received by the
slave.
No.
Function
Range
Unit Default
Type
F10.07
The Master
Communication
Sending Data
0:Input frequency
1:Output frequency
2:Primary numeric frequency
3:VP
4:VS
5:IS
0
〇
If setting F10.04=1, the inverter is the master, select frequency source sending from the
master to the slave via F10.07.
F10.07=0
The master sends input frequency.
F10.07=1
The master sends output frequency.
F10.07=2
The master sends primary numeric frequency.
F10.07=3
VP input voltage percentage sent by the master*Fmax
F10.07=4
VS input voltage percentage sent by the master*Fmax
F10.07=5
IS input current percentage sent by the master*Fmax
F11 Group: User Parameters
No.
Function
Range
Unit
Default
Type
F11.00
Parameter
Setting Control
0:Parameter setting permitted
1: Parameter lock 0
2: Parameter lock 1
0
〇
F11.01
User Password
0
~
65535
XXXXX
〇
F11.02
Parameter
Editing Mode
0:Editable via keypad and
RS485
1:Editable via keypad
2:Editable via RS485
0
〇
Parameter Setting Control
F11.00=0
Parameter setting permitted
F11.00=1
Parameter lock 0(Except F00.07 and F11.00, rest of the parameters cannot be
edited.)
Parameter lock 1(Except F11.00, rest of the parameters cannot be edited until the parameter
is unlocked.)
User Password
F11.01 is for setting a password to start password protection function to prevent parameters
from being edited by non-professionals. If the new password is 0, the password function is
disabled.
Parameter Editing Mode
F11.02=0
Editable via keypad and RS485
F11.02=1
Editable via keypad
F11.02=2
Editable via RS485.