User Manual
EM100 Mini Inverter
97
Figure 6-26
Output Overshoot Suppression
Figure 6-27
Output Periodic Oscillation Suppression
Output periodic oscillation suppression: Shorten the differentiation time GTd or set it as 0,
and reduce proportion gain GP, as shown in Figure 6-27.
No.
Function
Range
Unit
Default
Type
F09.10
PID Positive Output Limit
0.00
~
100.00
% 100.00
●
F09.11
PID Negative Output Limit
0.00
~
100.00
% 100.00
●
Set PID output percentage within the range of [-F09.11
,
F09.10]
No.
Function
Range
Unit Default
Type
F09.12
PID Feedback Loss
Detection Value
0.0
~
100.0
0.0: No detection on
feedback loss
% 0.0
●
F09.13
PID Feedback Loss
Detection Time
0.0
~
3000.0
S 1.0
●
F09.12/F09.13
are for PID feedback loss detection.
If PID feedback< PID feedback loss detection value (F09.12), and lasting time> PID
feedback loss detection time (F09.13), inverter trips PIDE (PID feedback loss) and will
take the corrective action based on selected troubleshooting. In order to prevent false alarm
of PIDE trip, please do not set F09.12=0.1 or 0.2.
F10 Group: Communication Parameters
EM100 supports Modbus protocol, RTU format, and processes single-master/ multi-slave
communication network of RS485 bus.
No.
Function
Range
Unit
Default
Type
F10.00
Inverter Address
1
~
247
0: Broadcasting address
1
〇
Inverter address code is the address code allocated to each inverter when the inverter is
connected to the PC/PLC network. Each address code is unique in this network. The
maximum number of inverter is 247 which are permitted to connect to the PC/PLC in one
network.
Output
After
Adjustment
Before
Adjustment
Time