Installing an AC Reactor
If power supply is connected to capacitive load, an excessive big surge current will occur
and rectifier of inverter can be broken down. Install an optional 3-phase/1-phase AC
reactor on input side of inverter to suppress peak current and voltage, and improve power
factor of the system.
Installing a Surge Absorber
Install a surge absorber for inductive loads (electromagnetic contactors, solenoid valves,
solenoid coils, or electromagnetic circuit breakers) nearby the inverter.
Countermeasure for Excessively Large Leakage Current(Only Applicable to
the products of SIZE3&SIZE4)
When the inverter is applied to the applications which are sensitive to leakage current,
for instance: civil application, malfunction of leakage protection switch is likely to occur.
Please loosen the screw anticlockwise on EMC terminal.
Installing a Noise Filter on Power Supply Side
To filter noise transmitted between power cable and the inverter, and the impact on
power grid caused by the noise produced by the inverter.
z
A special purpose noise filter is required for the inverter.
z
Correct vs incorrect installations of noise filters as shown in Figure 3-7 and Figure
3-8.
Figure 3-7 Correct Installation of Noise Filter
(
a
)
(b)
Figure 3-8 Incorrect Installation of Noise Filter