128
NO
Yes
Procedure
For SCV-750EB and SCV-1400EB
F2
Discharge temperature sensor connection
on main PCB is loose
Yes
Ensure the sensor is connected properly
No
Temperature or pressure sensor has
short-circuited or failed
Yes
Replace the sensor
Electronic expansion valve coil connection
on main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Electronic expansion valve coil has
malfunctioned
2
Yes
Replace the EXV
No
Discharge pressure is too high
Yes
The temperature difference between water
inlet and water outlet or water inlet is too
high
No
Yes
Replace outdoor main PCB
No
Water flow is insufficient
Yes
Refer to E9 error
Notes:
1.
Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 31, 32, 30 in Part 4, 2.2.1 Main PCB component).
2.
The normal resistances between EXV coil wiring terminals is 40-50Ω. If any of the resistances differ from the value, the EXV coil has malfunctioned.
Discharge pipe temperature sensor at the
top of the compressor falls or is not
insulated.
Ensure that the sensor is installed in an
accurate position and well insulated
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...