P3 troubleshooting
Digital display output
Description
P3 indicates ambient temperature too high for cooling mode
All units stop running.
Error code is only displayed on main PCB and user interface.
Possible causes
Ambient temperature sensor is interfered by other heat sources and the temperature detection value exceeds 65°C
Ambient temperature sensor damaged
Main control board damaged
Procedure
P3
Ambient temperature sensor is interfered
by other heat sources
Yes
Eliminate interfering heat source
No
Ambient temperature sensor
1
damaged
Yes
Replace Ambient temperature sensor
No
Replace main control board
Note:
1.
For SCV-750EB and SCV-1400EB, ambient temperature sensor connection port is CN30 on the main PCB (labeled 23 in Part 4, 2.2.1 Main PCB component).
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 4, 6.1 “Temperature Sensor Resistance Characteristics”.
2.
For SCV-900EB and SCV-1800EB, ambient temperature sensor connection port is CN1 on the main PCB
(labeled 29 in Part 4, 2.2.1 Main PCB component).
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 4, 6.1 “Temperature Sensor Resistance Characteristics”.
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...