5.23
F0 Troubleshooting
Digital display output
Description
1F0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2F0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Incorrect compressor inverter module address setting.
Loosened communication wiring from the main PCB to
the inverter module.
Bridge rectifier damaged.
Main PCB damaged.
Compressor inverter module damaged.
Procedure,
For SCV-750EB and SCV-1400EB
F0 error
Compressor inverter module address setting
is incorrect
Reset the compressor inverter
module address via dial switch
S7 on inverter module
1
Communication wire from outdoor main
PCB
CN26
to inverter module CN8/CN9 is
loosened
2
Reconnect the communication
wire
LED3 on inverter module are off when
power on
3
No
No
Yes
Yes
Check the power supply circuit
4
Yes
Replace the outdoor main PCB, is the
malfunction solved?
No
Normal
Yes
No
Replace the inverter module
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...