L11: Software overcurrent
Description
The current exceeds the OCP protection value (peak value) set by the software;
After the fault, the compressor stops running. If the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: It is detected that the compressor current exceeds the OCP protection value set by the software for three
consecutive carrier cycles.
Resume condition: The compressor shuts down after a fault, and resumes after reaching the fault exit condition one minute
later.
Reset method: Automatic recovery after reaching the fault exit condition one minute later.
Possible causes
There are impurities in the refrigerant system or the compressor is momentarily stuck, causing the current surge to trigger
OCP;
Module board Icd op amp sampling circuit is abnormal.
Procedure
L11
Drive board fault(swap the drive board to judge)
Yes
Change the drive board
NO
Impurities in the refrigerant system or the
compressor is momentarily stuck (noise when
running or starting)
Yes
Change the compressor
End
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...