For SCV-900EB and SCV-1800EB
H5
ODU power supply voltage at or above
265V or drops below 170V or a phase is
missing
1
Yes
Provide normal power supply
No
Wires between outdoor main PCB, AC filter
boards and electric control box power
supply terminals are loose
2
Yes
Ensure the wires are connected properly
No
High voltage circuit error has occurred,
such as the compressor has
malfunctioned
3
, the fan motor has
short-circuited
4
, or the inverter module has
short-circuited
5
Yes
Replace or repair the relevant parts
No
Replace outdoor main PCB
Notes:
1.
The normal voltage between A and N, B and N, and C and N is 207-253V.
2.
Refer to Part 4, 3 “Wiring diagram” and PCB components to make sure wire connection is firm.
3.
The normal resistances of the inverter compressor is 0.124Ω(at 20
℃
ambient temperature) among U V W and infinite between each of U V W and ground.
If any of the resistances differ from these specifications, the compressor has malfunctioned.
4.
The normal resistances of the fan motor coil among U V W are less than 15Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
5.
Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited. Refer to Part 4, 1 “Outdoor Unit Electric Control Box Layout”.
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...