150
Trigger/resume condition
Trigger condition: Open circuit of U-phase lower tube corresponding to compressor.
Resume condition: Check whether the IPM module is working.
Reset method: Change the module board. Power on and start up again.
Possible causes
There IPM module is damaged.
Procedure
Check whether the IPM virtual welding and the PWM related transmission circuit of the MCU are connected to the welding.
If so, change the replace the drive board.
6.19
L6c: Open circuit of V-phase upper tube
Description
Open circuit of V-phase upper tube.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: Open circuit of V-phase upper tube corresponding to compressor.
Resume condition: Check whether the IPM module is working.
Reset method: Change the module board. Power on and start up again.
Possible causes
There IPM module is damaged.
Procedure
Check whether the IPM virtual welding and the PWM related transmission circuit of the MCU are connected to the welding.
If so, change the replace the drive board.
6.20
L6d: Open circuit of V-phase lower tube
Description
Open circuit of V-phase lower tube.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: Open circuit of V-phase lower tube corresponding to compressor.
Resume condition: Check whether the IPM module is working.
Reset method: Change the module board. Power on and start up again.
Possible causes
There IPM module is damaged.
Procedure
Check whether the IPM virtual welding and the PWM related transmission circuit of the MCU are connected to the welding.
If so, change the replace the drive board.
6.21
L6E: Open circuit of W-phase upper tube
Description
Open circuit of W-phase upper tube.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: Open circuit of W-phase upper tube corresponding to compressor.
Resume condition: Check whether the IPM module is working.
Reset method: Change the module board. Power on and start up again.
Possible causes
There IPM module is damaged.
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...