P0 Troubleshooting
Digital display output
Description
Discharge pipe high pressure or discharge temperature switch protection. When the discharge pressure rises above 4.2MPa
or discharge temperature rises above 115°C, the system displays P0 protection and all units stop running. When the
discharge pressure falls below 3.2MPa or discharge temperature fall below 90°C, P0 is removed and normal operation
resumes. When P0 error occurs 3 times in 60 minutes, a manual system restart is required before the system can resume
operation.
Error code is displayed on main PCB and user interface.
Possible causes
High pressure switch or discharge temperature switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.