L20: Module overheat protection
Description
IPM module temperature exceeds 105 °C.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: IPM module temperature exceeds 105 °C;
Resume condition: The compressor shuts down after a fault, and resumes after reaching the fault exit condition (The
module temperature is lower than 105 °C) one minute later;
Reset method: Automatic recovery after reaching the fault exit condition one minute later.
Possible causes
IPM fixing screws are not tightened, resulting in poor heat dissipation;
The heat dissipation silicone of the IPM module is not evenly spread, resulting in poor heat dissipation;
The system lacks refrigerant or the refrigerant radiator pipeline is blocked, resulting in poor heat dissipation of the
refrigerant radiator;
The system refrigerant radiator is abnormally welded, resulting in too large thermal resistance and poor heat dissipation;
The module board IPM temperature detection circuit is abnormal.
Procedure
L20
IPM fixing screws are not tightened
Yes
Tighten IPM fixing screws
NO
The heat dissipation silicone is not applied or the
heat dissipation silicone is uneven
Yes
Reapply dissipation silicone
NO
The system lacks refrigerant (Use discharge
temperature and pressure to judge)
Yes
Refill refrigerant
NO
Refrigerant radiator clogged
Yes
Clean the pipe
NO
Drive board fault
Yes
Change the drive board
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...