80
5.6
E8 Troubleshooting
Digital display output
Description
Power supply phase sequence protector output error
When this error occurs in the main unit, all units stop running. When this error occurs in the slave unit, the slave unit stops
running.
Error code is displayed on main PCB and user interface.
Possible causes
Power supply phases not connected in correct sequence or lose.
Power supply terminals or Power phase protector wire connection loose.
Power supply abnormal.
Damaged main PCB.
Damaged power phase protector.