115
Procedure
PL/C7
The inverter compressor module
1
heat sink
is blocked or dirty
Yes
Clean or replace the heat sink
No
The screws connecting the heat sink to the
inverter module are loose
1
Yes
Tighten the screws and make sure the heat
sink is well-connected
No
Fan motor wiring connection is wrong
Yes
Check the fan motor wiring connection
No
Replace outdoor main PCB
Notes:
1.
Refer to Part 4, 1 “Electric Control Box Layout”.