103
Procedure
For SCV-750EB and SCV-1400EB
P7
Air side heat exchanger tube temperature
sensor “T3a / T3b” is loose
1
Yes
Ensure the temperature sensor is
connected properly
No
Fan motor wiring connection is wrong
Yes
Ensure fan motor wiring is connected
properly
No
Air side heat exchanger tube temperature
sensor “T3a / T3b” has short-circuited or
failed
2
Yes
Replace the temperature sensor
No
The air side heat exchanger heat exchange
is poor
3
Yes
Inspect the system and fix the error
No
The fan or fan motor is blocked or damaged
Yes
Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1.
Air side heat exchanger tube temperature sensor “T3a / T3b” connection port is CN37/CN16 on the main PCB (labeled 22,24 in Part 4, 2.2.1 Main PCB
component)
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 4, 6.1 “Temperature Sensor Resistance Characteristics”.
3.
Check air side heat exchanger, fan(s) and air outlets for dirt/blockages.
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...