67
Continued:
Code
Content
Remarks
PU
1PU DC fan A module protection
Displayed on main PCB and user interface
2PU DC fan B module protection
Displayed on main PCB and user interface
H9
1H9 Compressor A inverter module is not matched
Displayed on main PCB and user interface
2H9 Compressor A inverter module is not matched
Displayed on main PCB and user interface
HC
High pressure sensor error
Displayed on main PCB and user interface
HE
1HE No inset A valve error
Displayed on main PCB and user interface
2HE No inset B valve error
Displayed on main PCB and user interface
3HE No inset C valve error
Displayed on main PCB and user interface
F0
1FO IPM module A transmission error
Displayed on main PCB and user interface
2FO IPM module B transmission error
Displayed on main PCB and user interface
F2
Superheat insufficient
Displayed on main PCB and user interface
F4
1F4 module A L0 or L1 protection occurs for 3 times in 60 minutes
Displayed on main PCB and user interface
2F4 module B L0 or L1 protection occurs for 3 times in 60 minutes
Displayed on main PCB and user interface
F6
1F6 A system buss voltage error (PTC)
Displayed on main PCB and user interface
2F6 B system buss voltage error (PTC)
Displayed on main PCB and user interface
Fb
Pressure sensor error
Displayed on main PCB and user interface
Fd
Suction temperature sensor error
Displayed on main PCB and user interface
FF
1FF DC fan A error
Displayed on main PCB and user interface
2FF DC fan B error
Displayed on main PCB and user interface
FP
DIP switch inconsistency of multiple water pumps
Displayed on main PCB and user interface
C7
If PL occurs 3 times, the system reports the C7 failure
Displayed on main PCB and user interface
L0
Compressor inverter module protection (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L1
Low-voltage protection (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L2
High-voltage protection (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L4
MCE error (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L5
Zero speed protection (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L7
Phase sequence error (x=1or2) (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L8
Compressor frequency variation greater than 15Hz within one second protection
(for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
L9
Actual compressor frequency differs from target frequency by more than 15Hz
protection (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB
dF
Defrosting prompt (for
SCV-900EB and
SCV-1800EB)
Displayed on main PCB and user interface
bH
1bH Module 1 relay blocking or 908 chip self-check failed
Displayed on main PCB and user interface
2bH Module 2 relay blocking or 908 chip self-check failed
Displayed on main PCB and user interface
Summary of Contents for SCV-1400EB
Page 2: ......
Page 4: ...2...
Page 8: ...6...
Page 26: ...24...
Page 46: ...44 1 Electric Control Box Layout For SCV 750EB For SCV 1400EB...
Page 61: ...59 3 Wiring diagram 3 1 Single unit For SCV 750EB and SCV 1400EB...
Page 62: ...60 For SCV 900EB...
Page 63: ...61 For SCV 1800EB...
Page 78: ...76 5 5 E3 E4 E5 E7 Eb Ed EE EF EP EU Fb Fd Troubleshooting Digital display output...
Page 159: ......
Page 160: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...