SITRANS LR200 with mA/HART
82
Operating Instructions, 05/2019, A5E32337676-AE
5.
In Step 4 – Ranges, enter a value for maximum volume.
①
Breakpoints
②
Maximum volume
6.
Click on the Breakpoints tab and enter values for level and volume for up to 32
breakpoints.
7.
Navigate to Configure/Setup > Setup > Linearization and click on Characteristic to
preview the characteristic curve of the vessel breakpoints. (The conversion will function
correctly even if not all breakpoints are entered, but the curve will display correctly only if
all breakpoints are entered.)
8.
In Step 5 – Summary, check parameter values. Click on the appropriate step menu to
return and revise values, or click on a different menu to exit Quick Start.
Changing parameter settings using AMS Device Manager
Note
For a complete list of parameters, see Parameter reference (Page 97).
For more detailed explanations of the parameters listed below see the pages referenced.
1.
Adjust parameter values in the parameter value field in Configure/Setup view, then click
on Apply to write the new values to the device. The parameter field will display in yellow
until the value has been written to the device.
2.
Click on OK only if you wish to update all parameters and exit AMS.