SITRANS LR200 with mA/HART
78
Operating Instructions, 05/2019, A5E32337676-AE
Startup
1.
Launch AMS Device Manager. (Application Guides for setting up HART devices with
AMS Device Manager can be downloaded from our website:
www.siemens.com/LR200 (
2.
In Device Connection View right-click on the device icon and select Scan Device to
upload parameters from the device.
3.
Double click the device icon to open the startup screen. The startup screen shows device
identification details and a navigation window on the left side of the screen.
Master reset
Note
Device Address (5.1.) remains unchanged if the reset command is sent remotely (via AMS,
PDM, DTM, FC375) but is reset to 0 if the reset command is sent via HMI.
●
Navigate to Configure/Setup > Operation
●
In the General field click on Master Reset and accept the option Factory Defaults.