SITRANS LR200 with mA/HART
126
Operating Instructions, 05/2019, A5E32337676-AE
7.4.3.9
Acknowledge (4.3.9.)
Purpose:
Acknowledges the current maintenance reminder.
Description:
To acknowledge a reminder via SIMATIC PDM:
•
Open the menu Diagnostics > Device Diagnostics and click on the tab
Maintenance.
•
In the Calibration Schedule section, click on Acknowledge Warnings.
To acknowledge a reminder via the local control buttons or hand-held program-
mer:
•
Press RIGHT arrow twice to open parameter view and activate Edit Mode.
•
Press RIGHT arrow to acknowledge the reminder.
7.4.4
Service schedule (4.4.)
Note
•
Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up
Maintenance/Service schedules, based on operating hours instead of a calendar-based
schedule, see also Remaining device lifetime (4.2.) (Page 121), Remaining sensor
lifetime (4.3.) (Page 124), and Calibration schedule (4.5.) (Page 129).
•
Performing a reset to Factory Defaults will reset all the Maintenance Schedule
parameters to their factory defaults.
•
The device operates in years. To view Service Interval parameters in hours or days (via
SIMATIC PDM only) see Service interval (4.4.1.) (Page 127).
Factory setting:
years
Setting range
1)
:
Hours, days, years
Purpose:
The device tracks service intervals based on operating hours and monitors
the predicted lifetime to the next service. You can modify the Total Service
Interval, set schedules for maintenance reminders, and acknowledge them.
The maintenance warnings and reminders are communicated to the end
user through status information. This information can be integrated into any
Asset Management system. For optimal use, we recommend that you use
SIMATIC PCS7 Asset Management Software in conjunction with SIMATIC
PDM.
Description:
To access these parameters via SIMATIC PDM:
•
Open the menu Device – Maintenance and select the Service Schedule
tab.
•
After modifying values/units as required, click on Write to accept the
change, and Read to view the effect of the change.
•
Click on Service Performed to restart the timer and clear any fault mes-
sages.
1)
Selectable only via SIMATIC PDM.