7.4.3.3
Remaining lifetime (4.3.3.)
Read only. Lifetime expected (4.3.1.) (Page 124) less Time in operation (4.3.2.) (Page 124).
7.4.3.4
Reminder activation (4.3.4.)
Factory setting:
OFF
Setting range:
Reminder 1 (Maintenance Required), Reminder 2 (Maintenance Demand-
ed), Reminders 1 and 2, OFF
Purpose:
Allows you to enable a maintenance reminder.
Description:
To modify this parameter via SIMATIC PDM:
•
Go to menu Device – Maintenance.
7.4.3.5
Reminder 1 (required) (4.3.5.)
Factory setting:
0.164 years
Setting range:
0 to 20 years
Purpose:
If Remaining lifetime (4.3.3.) (Page 125) is equal to or less than this value,
the device generates a Maintenance Required reminder.
Description:
1) Modify values as required.
2) Set Reminder activation (4.3.4.) (Page 125).
7.4.3.6
Reminder 2 (demanded) (4.3.6.)
Factory setting:
0.019 years
Setting range:
0 to 20 years
Purpose:
If Remaining lifetime (4.3.3.) (Page 125) is equal to or less than this value,
the device generates a Maintenance Demanded reminder.
Description:
1) Modify values as required.
2) Set Reminder activation (4.3.4.) (Page 125).
7.4.3.7
Maintenance status (4.3.7.)
Indicates which level of maintenance reminder is active.
In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the
Maintenance tab, and check the Calibration Schedule Status window.
7.4.3.8
Acknowledge status (4.3.8.)
Indicates which level of maintenance reminder has been acknowledged.
In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the
Maintenance tab, and check the Calibration Schedule Status window.