SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
51
6.2.2.3
Sliding waveguide on anaerobic digesters
Note
•
Minimum distance from the flange face to the target is limited by Far range (2.8.2.)
(Page 111).
•
We recommend adjusting Auto False Echo Suppression parameters with an empty or
almost empty vessel.
This application is to obtain a level measurement and corresponding 4 to 20 mA output
proportional to the sludge level on a digester.
●
The raised position is for installation and maintenance.
●
The lowered position is for operation.
●
Program the instrument for operation in the lowered position.
●
Low Cal. Pt. is the bottom of the digester (10 m/33 ft from sensor reference point when
the instrument is lowered to its normal operating position).
●
High Cal.Pt. is 2 m (6.56 ft) from sensor reference point.
●
The maximum rate of filling or emptying is about 0.1 m (4")/min.
①
Sensor reference point
④
High calibration point
②
2 m
⑤
10 m
③
Horn
⑥
Low calibration point
Parameter type Parameter name (number)
Value
Function
Quick start
wizard parame-
ters
Material (1.2.)
LIQUID
Response Rate (1.3.)
MED
1 m/min. (3.28 ft/min.)
Units (1.4.)
M
meters
Operating Mode (1.5.)
LEVEL
Level
Low Calibration Point (1.6.)
10
10 m/33 ft)
High Calibration Point (1.7.)
2
2 m (6.56 ft)