7.2.3.2
Fill rate/min (2.4.2.)
Fill rate defines the maximum rate at which the reported sensor value
1)
is allowed to
increase. Allows you to adjust the device's response to increases in the actual material level.
Fill rate is automatically updated whenever Response rate (2.4.1.) (Page 101) is altered.
Note
Enter a value slightly greater than the maximum vessel-filling rate, in units per minute.
Response rate (2.4.1.) (Page 101)
Fill rate (2.4.2.)
Options
slow (factory setting)
0.1 m/min (0.32 ft/min)
medium
1.0 m/min (3.28 ft/min)
fast
10.0 m/min (32.8 ft/min)
Range
0 to 99999 m / min.
Related
parameter
Units (2.2.1.) (Page 99)
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target.
7.2.3.3
Empty rate/min (2.4.3.)
Empty rate defines the maximum rate at which the reported sensor value
1)
is allowed to
increase. Allows you to adjust the device's response to increases in the actual material level.
Empty rate is automatically updated whenever Response rate (2.4.1.) (Page 101) is altered.
Note
Enter a value slightly greater than the maximum vessel-emptying rate, in units per minute.
Response rate (2.4.1.) (Page 101)
Empty rate
Options
slow (factory setting)
0.1 m/min (0.32 ft/min)
medium
1.0 m/min (3.28 ft/min)
fast
10.0 m/min (32.8 ft/min)
Range
0 to 99999 m / min.
Related parameters Units (2.2.1.) (Page 99)
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target.