SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
49
Parameter type
Parameter no./name
Options/values Function
Quick start wizard
parameters
Material (1.2.)
LIQUID
Response Rate (1.3.)
MED
Medium =1 m/minute
Units (1.4.)
M
meters
Operating Mode (1.5.)
LEVEL
Level
Low Calibration Point (1.6.)
5
5 m (16.5 ft)
High Calibration Point (1.7.) 0.5
0.5 m (1.64 ft)
Apply? [Apply changes (1.8.)] YES
Transfers Quick Start set-
tings to device.
Independent param-
eters
Timer (2.5.2.) (Page 103)
2
2 minutes
(Page 103)
HI
Fail-safe level set to High
(Page 117)
Distance
1)
minus 0.42 m
(1.37 ft)
Sets length of learned TVT
2)
to use
sion (2.8.7.1.) (Page 115)
LEARN
Enables the use of learned
TVT
1)
Distance to product from sensor reference point.
2)
For more details, see Auto false echo suppression (2.8.7.1.) (Page 115) and Auto false
echo suppression range (2.8.7.2.) (Page 117).
Return to Measurement: press Mode to start normal operation.
6.2.2.2
Horizontal vessel with volume measurement
Note
•
Minimum distance from flange face to target is limited by Near range (2.8.1.) (Page 110).
•
We recommend using Auto False Echo Suppression with an empty or almost empty
vessel.
To obtain level measurement/4 to 20 mA output proportional to vessel volume in a chemical
vessel:
●
Low Calibration Point = 3.5 m (11.48 ft) from sensor reference point
●
High Calibration Point = 0.5 m (1.64 ft) from sensor reference point
●
Max. fill/empty rate = 0.2 m/min (0.65 ft/min)
Select vessel shape, Parabolic Ends, and enter values for A and L, to obtain a volume
reading instead of level.
In the event of a loss of echo: SITRANS LR200 is to go into Fail-safe High after 2 minutes.