SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
131
7.4.5.6
Reminder 2 (demanded) 4.5.6.)
Factory setting:
0.019 years
Setting range:
0 to 20 years
Purpose:
If Time until next calibration (4.5.3.) (Page 130) is equal to or less than this
value, the device generates a Maintenance Demanded reminder.
Description:
1.
Modify values as required.
2.
Set Reminder Activation (4.8.5.) (Page 130) to the desired option.
7.4.5.7
Maintenance status (4.5.7.)
Indicates which level of maintenance reminder is active.
In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the
Maintenance tab, and check the Calibration Schedule Status window.
7.4.5.8
Acknowledge status (4.5.8.)
Indicates which level of maintenance reminder has been acknowledged.
In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the
Maintenance tab, and check the Calibration Schedule Status window.
7.4.5.9
Acknowledge (4.5.9.)
Purpose:
Acknowledges the current maintenance reminder.
Description:
To acknowledge a reminder via SIMATIC PDM:
•
Open the menu Diagnostics > Device Diagnostics and click on the tab
Maintenance.
•
In the Calibration Schedule section, click on Acknowledge Warnings.
To acknowledge a reminder via the local control buttons or hand-held program-
mer:
•
Press RIGHT arrow twice to open parameter view and activate Edit Mode.
•
Press RIGHT arrow to acknowledge the reminder.
7.4.6
Manufacture date (4.6.)
The date of manufacture of the SITRANS LR200 (yy mm dd).
7.4.7
Powered hours (4.7.)
Displays the number of hours the unit has been powered up since manufacture. In SIMATIC
PDM, open the menu View – Wear.