SITRANS LR200 with mA/HART
48
Operating Instructions, 05/2019, A5E32337676-AE
Quick Start Parameter
Setting
Description
Vessel
STEEL
Selects vessel construction material.
Response Rate
SLOW
Resets fill rate and empty rate to 0.1 m/minute.
Units
m
Sensor measurement units.
Operation
LEVEL
Material level referenced from low calibration point
Low Calibration Point
15.5
Process empty level.
High Calibration Point
1.0
Process full level.
Wizard Complete
FINISH
Save new settings and exit Wizard
Note
•
Minimum distance from flange face to target is limited by Near range (2.8.1.) (Page 110).
•
We recommend using Auto False Echo Suppression with an empty or almost empty
vessel.
To obtain level measurement/4 to 20mA output proportional to resin levels:
●
Low Calibration Pt. = 5 m (16.5 ft) from sensor reference point
●
High Calibration Pt.= 0.5 m (1.64 ft) from sensor reference point
●
Max.fill/empty rate = 0.2 m/min (0.65 ft/min)
In the event of a loss of echo:
SITRANS LR200 is to go into Fail-safe High after 2 minutes.
①
Low calibration point
⑤
Sensor reference point
②
5 m
⑥
100% Level
③
High calibration point
⑦
0% Level
④
0.5 m