SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
191
Curve 2 (Flameproof, Increased Safety, Explosion-proof)
①
18.2V, 0
Ω
⑤
RL = 43.9*VL - 669.4
②
18.6V, 118
Ω
⑥
30V, 619
Ω
③
RL = 295*VL - 5369
⑦
Allowable operating area
④
24V, 355
Ω