SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
61
Using Linearization via the Quick Start Wizard
Open the menu Device - Wizard - Quick Start:
In Step 1 - Identification, click on Read Data from Device, select language, and click on Next.
In Step 2 – Application, select a volume application, for example Volume in a vessel, and
click on Next.
In Step 3 – Vessel Shape, choose the vessel shape option Linearization Table, and click on
Next.
In Step 4 - Ranges
①
Linearization
●
Enter parameter values.
●
Click on Linearization
●
In the Linearization window click on the appropriate Breakpoint tab to open the dialog
window.