SITRANS LR200 with mA/HART
100
Operating Instructions, 05/2019, A5E32337676-AE
7.2.1.4
Damping filter (2.2.4.)
Description
The time constant for the damping filter. The damping filter smooths out the
response to a sudden change in level. This is an exponential filter and the engi-
neering unit is always in seconds. For more detail, refer to Damping (Page 178).
Values
Range: 0 to 100.000 s
Factory setting
10.000 s
7.2.1.5
Antenna (2.2.5.)
Read only. Identifies antenna configuration (Near Range [blanking] distance is automatically
adjusted to suit).
7.2.2
Calibration (2.3.)
Note
We recommend using the Quick Start wizard to configure the device.
7.2.2.1
Low calibration point (2.3.1.)
Description
Distance from sensor reference point
1)
to Low Calibration Point. Units are de-
fined in Units.
Values
0 to 20 m
Factory setting
20.00 m
Related
parameters
Units (2.2.1.) (Page 99)
Far range (2.8.2.) (Page 111)
①
Sensor value
⑤
Low calibration point
②
Space
⑥
Far range
③
Distance
⑦
Level
④
High calibration point
1)
The point from which level measurement is referenced. Refer to Uni-construction
polypropylene rod antenna (Page 152) and Dimension drawing (Page 152).