SITRANS LR200 with mA/HART
108
Operating Instructions, 05/2019, A5E32337676-AE
Vessel shape
LCD Display/
description
Also required
FLAT SLOPED BOTTOM
maximum volume, dimension A
PARABOLIC ENDS
Parabolic end horizontal cylinder
maximum volume, dimension A,
dimension L
LINEAR TABLE
1)
Linearization
table (lev-
el/volume/breakpoints)
maximum volume, tables 1-32
level and volume breakpoints
Linearization Table must be selected in order for level/volume values to be transferred. For
more detail, refer to Table 1-8 (2.7.2.) (Page 109).
7.2.6.3
Maximum volume (2.7.1.2.)
Description
The maximum volume of the vessel. Enter the vessel volume corresponding to
High Calibration Point. For example, if your maximum vessel volume is 8000 L,
enter a value of 8000. Volume units are defined by the user but are not explicitly
stated in the device.
Values
Range: 0.0000 to 99999
Factory setting
100.0
Related
parameters
Low calibration point (2.3.1.) (Page 100)
High calibration point (2.3.2.) (Page 101)
Vessel shapes (2.7.1.1.) (Page 107)
7.2.6.4
Dimension A (2.7.1.3.)
Description
The height of the vessel bottom when the bottom is conical, pyramidal, parabol-
ic, spherical, or flat -sloped. If the vessel is horizontal with parabolic ends, the
depth of the end. For an illustration, refer to Vessel shapes (2.7.1.1.) (Page 107).
Values
0.0000 to 999999 mm
Factory setting
0.0
Related parame-
ters
UNITS (1.4.)
Vessel shapes (2.7.1.1.) (Page 107)