SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
103
7.2.4
Fail-safe (2.5.)
7.2.4.1
Material level (2.5.1.)
Material Level defines the mA output to use when the Fail-safe Timer expires.
STANDARD DEVICE
Options
HI
20.5 mA (max. mA Limit)
LO
3.8 mA (min. mA Limit)
HOLD (factory setting)
Last valid reading (default 22.6 mA)
VALUE
User-selected value (defined in LEVEL (2.5.3.)
NAMUR NE 43-COMPLIANT DEVICE
Options
HI
20.5 mA (max. mA Limit)
LO
3.8 mA (min. mA Limit)
HOLD
Last valid reading
VALUE
User-selected value (defined in LEVEL (2.5.3.):
default 3.58 mA)
Note
The default setting depends whether your device is a standard or NAMUR NE 43-compliant
device.
7.2.4.2
Timer (2.5.2.)
Description
Sets the time to elapse since the last valid reading, before the Fail-safe Material
Level is reported.
Values
Range: 0.00 to 720 seconds
Factory setting
100 s
Note
When a Loss of Echo occurs, Material level (2.5.1.) (Page 103) determines the material level
to be reported when the Fail-safe timer expires. For more detail, refer to Loss of Echo (LOE)
(Page 179).