Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
196
Manual, 04.2016, A5E35883207-7-76
Slot
Subslot Data
Description
Value range
Data size
System overload alarm
threshold time [ms]
Time delay before an alarm is
issued after a system overload was
detected.
0 - 60 000 ms
(default setting:
5 000 ms)
Unsigned16
Main power outage
alarm threshold time
[ms]
Time delay before an alarm is
issued after failure of the power
supply voltage (power supply
changes into the "Buffer mode").
0 - 60 000 ms
(default setting: 0 ms)
Unsigned16
Buffering disable
Buffer module was deactivated via
control command.
0 = false, 0 <> true
(default setting: false)
Unsigned8
Data block active
Indicator: Data block contains valid
data.
0 = false, 0 <> true
(default setting: false)
Unsigned8
0
3
Channel1 Utarget
[10 mV]
Currently set setpoint of the output
voltage for output 1.
4.0 V - 28.0 V
(default setting:
24.0 V)
Unsigned16
Channel1 Ilimit
[10 mA]
Response threshold of the output
current for output 1. When this is
exceeded, the output current is
interpreted as having an overload
condition and is shut down with a
time delay - or limited.
Output 5 A:
0.0 A - 5.0 A
(default setting: 5.0 A)
Output 10 A:
0.0 A - 10 A
(default setting: 10 A)
Unsigned16
Channel1 Ithreshold
Prewarning threshold of the config-
ured response threshold for the
output current in %. An alarm is
initiated when the actual output
current exceeds this value. Opera-
tion is continued without any re-
strictions. Prewarning is
deactivated by entering "0 %".
0 - 100 %
(default setting: 90 %)
Unsigned8
Channel1 Output
Enable
Switches output 1 on or off. A pos-
sible automatic shutdown due to
overload or power failure is not
taken into account.
0 = false, 0 <> true
(default setting: false)
Unsigned8
Channel1 Reset_In
Resets an overload shutdown for
this output
0 = false, 0 <> true
(default setting: false)
Unsigned8
Data block active
Indicator: Data block contains valid
data.
0 = false, 0 <> true
(default setting: false)
Unsigned8
0
4
Channel2 Utarget
[10 mV]
see data "Channel 1"
Channel2 Ilimit
[10 mA]
Channel2 Ithreshold
Channel2 Output
Enable
Channel2 Reset_In
Data block active
0
5
Channel3 Utarget
[10 mV]
see data "Channel 1"
Channel3 Ilimit
[10 mA]
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...