Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
216
Manual, 04.2016, A5E35883207-7-76
Index 0x0020: State information (reading)
Data
Description
Data type
Fill byte(s)
-
Unsigned16
Module operation state Operating state
0 = Off
Expansion module is
switched off
Unsigned8
1 = ErrorOff
The expansion module
was automatically shut
down as a result of opera-
tion under inadmissible
operating conditions.
2 = CooledDown
After an automatic shut-
down due to a fault, the
expansion module can be
reactivated by switching
off and switching on the
supply voltage.
3 = Boot
The expansion module is
powering up, all of the
outputs are still switched
off.
4 = Running
The expansion module is
operating in the normal
mode.
5 = Buffering
Primary supply voltage
has failed. The expansion
module is operating in the
buffer mode.
Channel1 Utarget
[10mV]
Currently set setpoint of the output voltage for output 1.
Unsigned16
Channel1 Ilimit
[10 mA]
Response threshold of the output current for output 1. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Unsigned16
Channel1 Ithreshold
(0-100%)
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
Unsigned8
Fill byte(s)
-
Unsigned8
Channel1 output
voltage [10mV]
Output voltage at output 1.
Unsigned16
Channel1 output
current [10mA]
Output current at output 1.
Unsigned16
Channel1 max output
current [10mA]
Maximum output current at output 1.
Unsigned16
Channel1 Operation
mode
Operating mode output 1:
If the actual load current
of an output exceeds the
specified response
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
Unsigned8
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...