
Engineering and remote access
7.3 SIMATIC STEP 7 in the TIA Portal
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
139
Changing the IP address of a SITOP PSU8600
1.
Select the PROFINET interface of a PROFINET device in the Network or Device view of
the Hardware and Network editor of STEP 7 in the TIA Portal.
2.
In the Inspector window navigate to "Ethernet addresses" in the "IP protocol" area.
3.
Check whether the "Set IP address in the project" option is activated.
4.
Enter the new IP address in the appropriate field.
Loading the configuration to the SITOP PSU8600
For commissioning, you must load the project data that you created offline into the
connected SITOP PSU8600. This project data results from the configuration of the hardware,
networks and connections in STEP 7.
Initially, the complete project data is loaded. Only the changes are subsequently loaded.
Preconditions
●
The project data is consistent.
●
The Device name must be identical, offline and online.
●
The SITOP PSU8600 is accessible online.
●
The SITOP PSU8600 is located in the PROFINET IO system of an IO controller.
●
The PG/PC is connected to the same network to which the SITOP PSU8600 and the
controller are connected. The interface of the PG/PC must be set to TCP/IP.
Note
Ensure that the article number of the SITOP PSU8600 configured offline matches the article
number of the device connected online.
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...