Installation and maintenance
4.6 System response for a modified hardware configuration
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
93
Case 1
Replacement using a module with the same function (a buffer module by buffer module,
expansion module by expansion module):
●
A compatibility check is carried out for buffer modules:
–
If a buffer module with electrolytic capacitors is replaced by a buffer module with
electrolytic capacitors, then the new module is automatically commissioned.
–
If a buffer module with double-layer capacitors is replaced by a buffer module with
double-layer capacitors, then a more powerful module is automatically commissioned.
A module with a lower power rating is deactivated (LED "OK" flashes red). You can
activate this module by loading a corrected configuration via the associated control
system.
–
If a buffer module with electrolytic capacitors is replaced by a buffer module with
double-layer capacitors - or vice versa - then the new module is automatically
deactivated ("OK" LED flashes red). You can activate this module by loading a
corrected configuration via the associated control system.
●
For expansion modules, a compatibility check is carried out:
–
For expansion modules with a higher power rating, after switching on again, the
outputs are in the operating state "manually shutdown" (the LEDs of the outputs are lit
yellow).
The outputs are switched-on by pressing their associated buttons.
–
Expansion modules with a lower power rating are deactivated (LED "OK" flashes red,
LEDs of the outputs are dark).
You can activate these modules by loading a corrected configuration via the
associated control system.
Case 2
Replacement using a module with a different function (a buffer module by an expansion
module, or vice versa):
●
The new module is deactivated (LED "OK" flashes red, LEDs of the expansion module
outputs are dark).
You can activate the module by loading a correct configuration via the associated control
system.
See also
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...